SECTION 26 27 28
DISCONNECT SWITCHES
PART 1 - GENERAL
SCOPE
The work under this section includes disconnect switches, fuses and enclosures. Included are the following topics:
PART 1 - GENERAL
Scope
Related Work
References
Submittals
Operation and Maintenance Data
General
PART 2 - PRODUCTS
Disconnect Switches
Fuses
PART 3 - EXECUTION
Installation
Construction Verification Items
RELATED WORK
Applicable provisions of Division 1 govern work under this Section.
Section 26 27 02 - Equipment Wiring Systems
Section 26 08 00 - Commissioning of Electrical
REFERENCES
NECA (National Electrical Contractors Association) "Standard of Installation"
NEMA KS 1 – Enclosed Switches
UL 50 – Enclosures for Electrical Equipment
UL 98 – Enclosed and Dead-front Switches
SUBMITTALS
Include outline drawings with dimensions, and equipment ratings for voltage, ampacity, horsepower, and short circuit.
OPERATION AND MAINTENANCE DATA
All operations and maintenance data shall comply with the submission and content requirements specified under section GENERAL REQUIREMENTS.
GENERAL
Provide disconnect switches for loads required by code. Review HVAC and Plumbing specifications to determine what equipment is furnished with disconnect switches. Install disconnect switches whether furnished under this contract or not. It is the Electrical Contractors responsibility to determine the need for a disconnect switch for each load. The contractors shall include in their bid the code required disconnect switches whether indicated on the drawings or not.
PART 2 - PRODUCTS
DISCONNECT SWITCHES
Fusible Switch Assemblies: NEMA Type Heavy Duty; quick‑make, quick‑break, load interrupter, enclosed knife switch with externally operable handle interlocked to prevent opening front cover with switch in ON position. Handle lockable in OFF position. Fuse Clips: designed to accommodate Class R, Class J or Class CC (motors) cartridge type fuses.
Nonfusible Switch Assemblies: NEMA Type Heavy Duty; quick‑make, quick‑break, load interrupter, enclosed knife switch with externally operable handle interlocked to prevent opening front cover with switch in ON position. Handle lockable in OFF position.
Enclosure:
Indoor: NEMA 1 code gauge steel with rust inhibiting primer and baked enamel finish.
Outdoors: NEMA 3R code gauge zinc coated steel with baked enamel finish or NEMA 4 when indicated on drawings.
Corrosive Areas, Kitchen/Food service areas, Therapeutic/Pool spaces and Damp/Wet locations: NEMA Type 4X, 304 stainless steel with brushed finish.
Provide manufacturer’s equipment ground kit in all disconnect switches.
In applications where the switch serves as the service entrance disconnect, provide service ground kit, label as service disconnect and provide UL listing for service disconnect.
FUSES
Fuses 600 Amperes and Less: Dual element, time delay, [250] [600] volt, UL Class [RK 1.] [RK 5.] [J.] Interrupting Rating: 200,000 rms amperes.
Fuses 601 Amperes and Larger: Low Peak, time delay, 600 volt, UL Class L. Interrupting Rating: 200,000 rms amperes.
Fuses 30 Amperes and less: Time-Delay, 600 volt, UL Class CC. Interrupting rating: 200,000 rms amperes.
Provide three (3) spares of each size and type fuse.
Provide cabinet/enclosure for spare fuses sized to accommodate all required spare fuses for entire facility. Cabinet shall have hinged and latched cover. Label cabinet “Spare Fuses”. Locate cabinet in main electrical room.
PART 3 - EXECUTION
INSTALLATION
Install disconnect switches where indicated on Drawings or required by NEC.
Provide identification as specified in Section 26 05 53.
Provide label on inside of disconnect cover identifying the type and size of fuse to be utilized.
CONSTRUCTION VERIFICATION
Contractor is responsible for utilizing the construction verification checklists supplied under specification Section 26 08 00
END OF SECTION